There are two scenarios where Raters are required to verify the register boots have been sealed to the surrounding material.
When register boot sealing is mandatory
- New duct system – when the duct system being tested for duct leakage meets the CEC’s definition of a new duct system i.e. 75% or more of the duct system is new and the remaining 25% is accessible and can be sealed, the register boots MUST be sealed.
- Sealing all accessible leaks, smoke and visual verification – For altered or existing duct systems that are unable to pass either the total duct leakage test at 10% or the leakage to outside test at 7%, and the system is being passed by the seal all accessible leaks, smoke and visual verification protocol, the register boots MUST be sealed.
Bottom Line
New duct system: register boots must be sealed!
Pass by smoke: register boots must be sealed!
How to seal register boots
Sealing on HVAC Installation